In shell-and-tube heat exchangers, the temperature difference between the fluids inside and outside the tubes leads to a temperature difference between the shell and the tube bundle. If the temperature difference is large, significant thermal stress will be generated within the heat exchanger, causing the tubes to bend, break, or detach from the tube sheet. Therefore, when the temperature difference between the tube bundle and the shell exceeds 50°C, appropriate compensation measures are required to eliminate or reduce thermal stress. Based on the compensation measures employed, shell-and-tube heat exchangers can be classified into the following main types:
① Fixed tube sheet heat exchanger: The tube sheets at both ends of the tube bundle are integrated with the shell. This structure is simple but only suitable for heat exchange operations where the temperature difference between the hot and cold fluids is small and the shell side does not require mechanical cleaning. When the temperature difference is slightly larger and the shell-side pressure is not too high, elastic compensation rings can be installed on the shell to reduce thermal stress.
② Floating head heat exchanger: The tube sheet at one end of the tube bundle can float freely, completely eliminating thermal stress; and the entire tube bundle can be extracted from the shell for easy mechanical cleaning and maintenance. Floating head heat exchangers are widely used, but their structure is relatively complex and their cost is high.
③ U-tube heat exchangers: Each heat exchange tube is bent into a U-shape, with both ends fixed to the upper and lower sections of the same tube sheet, separated into inlet and outlet chambers by baffles within the tube box. This type of heat exchanger completely eliminates thermal stress and has a simpler structure than floating head heat exchangers, but the tube side is difficult to clean.
④ Vortex heat film heat exchangers: Vortex heat film heat exchangers utilize the latest vortex heat film heat transfer technology. By changing the fluid motion state, they increase the heat transfer effect. When the medium passes over the surface of the vortex tubes, it strongly scours the tube surface, thereby improving the heat transfer efficiency. The maximum efficiency can reach 10000 W/m²℃. This structure also achieves corrosion resistance, high temperature resistance, high pressure resistance, and anti-scaling functions. Other types of heat exchangers have a fixed-direction flow pattern in the fluid channel, forming a flow around the heat exchange tube surface, which reduces the convective heat transfer coefficient.